UPS 6~10 KVA SRP

UPS 6~10 KVA SRP

مشخصات فنی

FEATURES:

High frequency on-line double conversion technologyAuto sensing frequency
DSP (Digital Signal Processor) control technology50/60 Hz frequency conversion
Active power factor correction (APFC), input power factor up to 0.99Cold start
Output power factor 0.9Linear derating in low voltage input reducing battery discharging times
Wide input voltage range (110 V ~ 300 Vac) and frequency range (40~70Hz)Settable delayed start when power is restored
Rear ventilation design and variable speed fanAdvanced battery management (ABM)
Effective software and hardware protectionMultiple function settable via LCD: output voltage, battery quantity, EOD, EPO, ECO mode, frequency conversion mode and parallel enable
Quick and stable charging, 90% capacity restored in 4 h (standard model UPS)Powerful background software for parameters configuration, function setting and online updating
Multi platform communications: RS232 (standard), USB / RS485, SNMP / dry contacts (optional)

Flexible battery configuration (Settable 14-20 pcs batteries)

AVAILABLE OPTIONS:

Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS Alarms, EPO function, maintenance bypass, EPO function, parallel function, battery temperature compensation and EMD environmental sensor

SPECIFICATIONS:

MODEL

SRP 6I

SRP 6E

SRP 10I

SRP 10E

Capacity6 KVA/5400W10 KVA/9000W

INPUT

Rated voltage208V / 220V / 230V / 240 Vac
Voltage range110~160 Vac (linear derating between 50% and 100% load); 160~280 Vac (no derating); 280~300 Vac (derating 50%)
Rated frequency50/60 Hz (auto-sense)
Frequency range40~70Hz
Power factor>0.99
Total harmonic distortion (THDV)<5%
Bypass voltage range-40%~+15% (settable)

OUTPUT

Voltage208V / 220V / 230V / 240 Vac (settable)
Voltage regulation± 1%
Frequency45~55Hz or 55~65Hz (synchronized range); 50/60 Hz ± 0.1 Hz (battery mode)
WaveformPure sine wave
Crest factor3:01
Total harmonic distortion (TDHv)< 2% (linear load); < 5% (non-linear load)
Transfer timeMains mode to battery mode: 0 ms; Inverter mode to bypass mode: 0 ms
Inverter overload capability102~125%: Transfer tp bypass in 10 mins; 125~150%: Transfer to bypass in 1 min; > 150%: Transfer to bypass in 1 s
Bypass overload capability102~125%: Transfer tp bypass in 10 mins; 125~150%: Shutdown in 1 min; > 150%: Shutdown in 1 s

BATTERIES

DC voltage182 VDC (168 / 180 / 192 / 204 / 216 / 228 / 240 VDC optional)
Inbuilt battery16×9 Ah/16×9 Ah/
Recharge timeStandard model (S): 90% capacity restored in 4 hours: Long time model (H): depend on the capacity of battery

SYSTEM

Efficiency> 93%, ECO mode 98%
DisplayLCD + LED
AlarmsBattery mode, Battery voltage low, fans fault etc.
Maximum parallel numbers6
EMIIEC/EN62040-2
EMSIEC61000-4-2 (ESD), IEC61000-4-3 (RS), IEC61000-4-4 (EFT), IEC61000-4-5 (Surge)

COMMUNICATIONS

RS232/ USB/ RS485/ dry contactSupports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10
SNMPPower management from SNMP manager and web browser

OTHERS

Humidity20~90% RH @ 0~40°c (non-condensing)
Noise level< 55dB (1m)
Dimensions (WxDxH) (mm)191x462x710191x462x350191x462x710191x462x350
Packaged Dimensions (WxDxH) (mm)308x640x896267x573x436308x640x896267x573x436
Net weight (kg)58.715.667.216.1
Gross weight (kg)64.817.973.318.4
Ideate capacity to 70% in frequency conversions mode and to 90% when the output voltage is adjusted to 208 Vac.
S means standard model. H means long time model.
All specifications subject to change without notice.
Custom-mode specifications are acceptable.